| Frame sizes
200-280, supply 3300/3/50 |
|
| Performance data |
|
|
| Frame size |
Poles |
Output |
Power factor |
Efficiency |
FLC |
LRC |
LRT |
FL speed |
|
| kW |
4/4 |
3/4 |
2/4 |
4/4 |
3/4 |
2/4 |
A |
%FLC |
%FLT |
RPM |
|
| D/E200 |
2 |
15 |
0.91 |
0.89 |
0.83 |
87.0 |
86.0 |
83.0 |
3.3 |
800 |
130 |
2965 |
|
| D/E225A |
2 |
20 |
0.90 |
0.86 |
0.77 |
89.0 |
88.0 |
85.0 |
4.4 |
800 |
130 |
2968 |
|
| D/E225B |
2 |
25 |
0.90 |
0.88 |
0.82 |
90.0 |
89.5 |
87.5 |
5.4 |
750 |
120 |
2965 |
|
| D/E225C |
2 |
30 |
0.90 |
0.88 |
0.81 |
91.0 |
90.5 |
88.5 |
6.4 |
800 |
140 |
2968 |
|
| D/E250A |
2 |
37 |
0.89 |
0.86 |
0.80 |
91.0 |
90.0 |
87.0 |
8 |
750 |
120 |
2970 |
|
| D/E250B |
2 |
45 |
0.90 |
0.89 |
0.84 |
91.5 |
91.0 |
89.0 |
9.6 |
700 |
110 |
2970 |
|
| D/E250C |
2 |
57 |
0.90 |
0.89 |
0.84 |
92.5 |
92.0 |
90.0 |
12 |
775 |
130 |
2970 |
|
| D/E280A |
2 |
75 |
0.90 |
0.87 |
0.80 |
92.5 |
91.5 |
90.0 |
15.8 |
750 |
180 |
2965 |
|
| D/E280B |
2 |
90 |
0.90 |
0.87 |
0.80 |
93.0 |
92.5 |
91.0 |
18.8 |
750 |
180 |
2965 |
|
|
|
| D/E200 |
4 |
15 |
0.86 |
0.82 |
0.74 |
89.0 |
88.5 |
87.0 |
3.4 |
650 |
140 |
1476 |
|
| D/E225A |
4 |
20 |
0.87 |
0.84 |
0.77 |
89.5 |
89.0 |
87.0 |
4.5 |
650 |
140 |
1475 |
|
| D/E225B |
4 |
25 |
0.87 |
0.84 |
0.77 |
90.5 |
90.0 |
88.0 |
5.6 |
700 |
150 |
1476 |
|
| D/E225C |
4 |
30 |
0.86 |
0.83 |
0.75 |
91.0 |
91.0 |
89.0 |
6.7 |
750 |
160 |
1479 |
|
| D/E250A |
4 |
37 |
0.83 |
0.79 |
0.70 |
92.0 |
91.5 |
89.0 |
8.5 |
750 |
160 |
1482 |
|
| D/E250B |
4 |
45 |
0.85 |
0.82 |
0.75 |
92.5 |
92.0 |
90.5 |
10 |
700 |
150 |
1481 |
|
| D/E250C |
4 |
57 |
0.85 |
0.82 |
0.74 |
93.0 |
92.5 |
91.3 |
12.6 |
750 |
160 |
1483 |
|
| D/E280A |
4 |
75 |
0.87 |
0.83 |
0.75 |
93.0 |
93.0 |
91.5 |
16.2 |
675 |
200 |
1477 |
|
| D/E280B |
4 |
90 |
0.86 |
0.82 |
0.73 |
93.5 |
93.5 |
92.0 |
19.6 |
725 |
210 |
1479 |
|
|
| All
motors are class F insulation, with temperature rise limited to class B (80K)
and for use in a maximum ambient temperature of 40 Degrees C |
|
| Available
in both safe area and underground mining configurations |
|
| All
rotors are fabricated copper, Barlok pinned bar construction for arduous
applications |
|
| Intermediate
outputs, special performance requirements and mechanical modifications can be
accomodated - please contact us for more information |
|
| |
|
|
|
50 Hz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|